1. Attach the receiver next to the irrigation controller using the two
stainless steel screws provided (Fig. 2). Where appropriate, foam tape
(provided) can be used to attach the receiver.
Warning: Disconnect 24 VAC power to controller before connecting
receiver. DO NOT connect receiver to 110/220 VAC (house current).
2. Routethereceivercableintothecontrollercabinet.
Note: If your controller has a sensor bypass switch, make sure
itissettoenablethesensor.Referto
the irrigation controller’s user guide
for specifics.
3. Connect the receiver per the applicable
wiring diagram (Fig. 3a or 3b).
*Note:ForaNormallyOpensensor
application, connect the Yellow wire in
place of the Brown wire.
4. Applypowertocontroller. The receiver
will appear as shown below when power
is first applied. If the display and LED are
noton,checktheRedwireconnections.
3
Step 2 - Install and Connect the Receiver
Remove
Jumper
Red
Red
Brown
White
Receiver Cable
24 VAC
Controller with Sensor Terminals
Yellow (see *Note)
Yellow (not used)
Transformer
(power to the controller)
Fig. 3a
Fig. 2
Transformer
(power to the controller)
Fig. 3b
Controller without Sensor Terminals
Brown
White
Red
Red
Valve
Common
from Field
Receiver Cable
24 VAC
Valve Common
Rain Sensor Terminal